[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-881797":3},{"question":4,"library":27},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":25,"analysis":26},881797,569,2,"多选题","根据消防设计规范对通风、空调系统的风管上应设置防火阀的要求，下列哪几项是正确的？( )",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","发电机房储油间的排风管穿越储油间的隔墙处，应设置280℃的排烟防火阀",false,{"key":16,"text":17,"correct":18},"B","发电机房储油间的排风管穿越储油间的隔墙处，应设置70℃的防火阀",true,{"key":20,"text":21,"correct":18},"C","连接排风竖井的卫生间排风支管上，应设置70℃的防火阀",{"key":23,"text":24,"correct":14},"D","连接戊类库房的排风支管上，应设置70℃的防火阀","BC","",{"id":6,"name":28,"category":29,"favorite":30},"专业知识（暖通空调专业）","建筑工程",0]