[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-881792":3},{"question":4,"library":27},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":25,"analysis":26},881792,569,2,"多选题","计算工业厂房的自然通风，确定厂房上部窗孔排风温度时，哪几项是错误的？",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","对于某些特定的车间，可按排风温度与夏季通风室外计算温度的允许温差确定",false,{"key":16,"text":17,"correct":18},"B","对于厂房高度小于15m，室内散热量比较均匀，可取室内空气的平均温度",true,{"key":20,"text":21,"correct":18},"C","对于厂房高度大于15m，室内散热量比较均匀，且散热量不大于116W\u002Fmz，可按温度梯度法计算排风温度",{"key":23,"text":24,"correct":14},"D","有强烈热源的车间，可按有效散热系数法计算确定","BC","",{"id":6,"name":28,"category":29,"favorite":30},"专业知识（暖通空调专业）","建筑工程",0]