[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-881741":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},881741,569,1,"单选题","设置于地下室、半地下室使用燃气的厨房，其独立的机械送排风系统所选取的通风换气量，下列哪一项是错误的？",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","正常工作时，换气次数不应小于6次\u002Fh",false,{"key":16,"text":17,"correct":18},"B","事故通风时，换气次数不应小于10次\u002Fh",true,{"key":20,"text":21,"correct":14},"C","不工作时，换气次数不应小于3次\u002Fh",{"key":23,"text":24,"correct":14},"D","当燃烧所需的空气由室内吸取时，同时应满足燃烧所需的空气量","《城镇燃气设计规范》GB50028-2006第10.5.3条：应设置独立的机械送排风系统；通风量应满足下列要求：(1)正常工作时，换气次数不应小于6次\u002Fh；事故通风时，换气次数不应小于12次／h；不工作时换气次数不应小于3次\u002Fh；(2)当燃烧所需的空气由室内吸取时，应满足燃烧所需的空气量；(3)应满足排除房间热力设备散失的多余热量所需的空气量。",{"id":6,"name":27,"category":28,"favorite":29},"专业知识（暖通空调专业）","建筑工程",0]