[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-881739":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},881739,569,1,"单选题","对某新建居住小区设街区水一水换热站，小区内建筑均为低温热水地板辐射供暖系统，下列补水量估算和补水泵台数的确定，正确的是何项?( )。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","每台按供暖系统水容量的1%～2%，3台(两用一备)",false,{"key":16,"text":17,"correct":18},"B","每台按供暖系统循环水容量的1%～2%，2台",true,{"key":20,"text":21,"correct":14},"C","每台按供暖系统水容量的2%～3%，2台",{"key":23,"text":24,"correct":14},"D","每台按供暖系统循环水容量的2%～3%，3台(两用一备)","(1)《城镇供热管网设计规范》CJJ34-2010第10.3.8条。注意条文解释很重要：正常补水量按系统水容量计算较合理，但热力站设计时系统水容量统计有时有一定难度。本次修订给出按循环水量和水温估算的参考值。(2)间接连接采暖系统，当设计供水温度等于或低于65℃时，可取循环流量的1%～2%。补水泵的台数不应少于两台，可不设备用泵。(3)《民规》第8.5.15条、第8.5.16条：空调冷热水的小时泄漏量宜按水容量的1%计算。补水泵总小时流量宜为系统水容量的5%。补水泵总小时流量宜为系统水容量的5%～10%。《民规》第8.5.16条：空调系统补水泵宜设置2台。当设置1台且在严寒和寒冷地区空调冷热水合用补水泵时宜设置备用泵。",{"id":6,"name":27,"category":28,"favorite":29},"专业知识（暖通空调专业）","建筑工程",0]