[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-881682":3},{"question":4,"library":27},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":25,"analysis":26},881682,569,2,"多选题","冷库中制冷管道的敷设要求，下列哪几项是错误的?( )。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","低压侧制冷管道的直管段超过120m，应设置一处管道补偿装置",true,{"key":16,"text":17,"correct":18},"B","高压侧制冷管道的直管段超过50m，应设置一处管道补偿装置",false,{"key":20,"text":21,"correct":14},"C","当水平敷设的回气管外径大于108mm时，其变径管接头应保证顶部平齐",{"key":23,"text":24,"correct":14},"D","制冷系统的气液管道穿过建筑楼板、墙体时，均应加套管，套管空隙均应密封","ACD","根据《冷库设计规范》GB50072-2010第6.5.7条第1款中所述，选项A中“120m”应为“100m”，故选项A错误；选项B正确；由第6款所述，选项C应为底部平齐，故选项C错误；由第2款所述，制冷剂管道穿过建筑物的墙体(除防火墙外)、楼板、屋面时，应加套管，套管与管道间的空隙应密封但制冷压缩机的排气管道与套管间的间隙不应密封。从规范的意思可知：一、穿越防火墙是不需要加套管，二、制冷压缩机的排气管道与套管间的间隙不应密封，所以选项D是错误的。",{"id":6,"name":28,"category":29,"favorite":30},"专业知识（暖通空调专业）","建筑工程",0]