[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-881680":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},881680,569,1,"单选题","某栋楼的空调水系统，冷水机组的阻力为100kPa，管道为异程系统，最远环路的阻力最大，其单程长度50m，比摩阻均按150Pa\u002Fm估算，局部阻力为摩擦阻力的50%，过滤器、分集水器等管道附件的阻力为80kPa，最远环路空调末端阻力为43kPa，则循环水泵的扬程应选( )。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","24m",false,{"key":16,"text":17,"correct":14},"B","26m",{"key":19,"text":20,"correct":21},"C","28m",true,{"key":23,"text":24,"correct":14},"D","30m","循环水泵扬程的安全因数取1.1。管道为异程系统，最远环路的总管长为两倍单程管长。因此循环水泵的扬程为：H=(50×2×0.15+100+80+43)×1.1／103×9.8m=27.6m",{"id":6,"name":27,"category":28,"favorite":29},"专业知识（暖通空调专业）","建筑工程",0]