[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-881665":3},{"question":4,"library":27},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":25,"analysis":26},881665,569,2,"多选题","多联机空调系统制冷剂管道的气密性试验做法，下列哪几项不符合规定?( )。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","R410A高压系统试验压力为3.0MPa",true,{"key":16,"text":17,"correct":18},"B","应采用干燥压缩空气或氮气",false,{"key":20,"text":21,"correct":18},"C","试验时要保证系统的手动阀和电磁阀全部开启",{"key":23,"text":24,"correct":14},"D","系统保压经24h后，当压力降大于试验压力2%时，应重新试验","AD","根据《多联机空调系统工程技术规程》JGJ174-2010第5.4.10条中表5.4.10可知，R410A高压系统试验压力为4.OMPa，故选项A是错误的；选项B、C是正确的；选项D中应该为：当压力降大于试验压力1%时，应重新试验，故选项D错误。",{"id":6,"name":28,"category":29,"favorite":30},"专业知识（暖通空调专业）","建筑工程",0]