[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-881645":3},{"question":4,"library":27},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":25,"analysis":26},881645,569,2,"多选题","某空调冷水系统采用两台蒸汽压缩式冷水机组，配置的一次定流量循环水泵，冷却水泵与冷却塔并联运行。当因气候变化，部分负荷运行时，仅有一台机组与其相匹配的水泵等运行。实现节能，并保障运行合理的做法应是下列哪几项？",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","关闭不运行冷水机组的冷却水进机组管路阀门",true,{"key":16,"text":17,"correct":14},"B","关闭不运行冷水机组的冷水进机组管路阀门",{"key":19,"text":20,"correct":21},"C","始终使冷却水通过两台冷却塔实现冷却",false,{"key":23,"text":24,"correct":21},"D","两台冷却塔的风机保持全部运行","AB","",{"id":6,"name":28,"category":29,"favorite":30},"专业知识（暖通空调专业）","建筑工程",0]