[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-881635":3},{"question":4,"library":27},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":25,"analysis":26},881635,569,2,"多选题","",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","水泵的设计扬程不够",false,{"key":16,"text":17,"correct":18},"B","水泵的设计流量不够",true,{"key":20,"text":21,"correct":18},"C","热水系统的设计阻力过小",{"key":23,"text":24,"correct":14},"D","水泵性能未达到要求","BC","根据计算，设计流量满足房间供热要求。实际运行时，供回水温差增大，且供热量不足，表明实际流量小于设计流量，流速降低，管道阻力损失降低，所以实际扬程下降至12m。因此可能的原因是管道系统的阻力计算不准确，阻力损失过大，设计扬程20米不够。或是水泵性能未达到设计要求。",{"id":6,"name":28,"category":29,"favorite":30},"专业知识（暖通空调专业）","建筑工程",0]