[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-881615":3},{"question":4,"library":27},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":25,"analysis":26},881615,569,2,"多选题","根据供回水干管末端压差，变频调速控制空调冷水二级泵，系统环路常出现大流量小温差的现象，不利于空调系统节能。下列哪些分析判断是正确的？",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","干管末端压差设定值偏大",true,{"key":16,"text":17,"correct":14},"B","大部分自控水量调节阀故障，无法关闭",{"key":19,"text":20,"correct":14},"C","空调箱盘管选型偏小",{"key":22,"text":23,"correct":24},"D","二次供水温度偏低",false,"ABC","出现大流量现象。",{"id":6,"name":28,"category":29,"favorite":30},"专业知识（暖通空调专业）","建筑工程",0]