[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-881611":3},{"question":4,"library":27},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":25,"analysis":26},881611,569,2,"多选题","关于湿空气处理过程的表述，下列哪几项是错的？",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","室内发热量很大且无余湿量，冬季送风温度为15℃，采用干蒸汽加湿可保证室内25℃、60%的参数",true,{"key":16,"text":17,"correct":14},"B","北方地区的一次回风系统中，当冬季新风温度太低时，需预热新风后再与回风混合，以防止冻坏加热盘管",{"key":19,"text":20,"correct":21},"C","空调箱中加设循环水喷淋段，可以在过渡季减少冷机开启时间",false,{"key":23,"text":24,"correct":14},"D","直接蒸发冷却获得的最低水温为空气的湿球温度，间接蒸发冷却可以获得低于空气露点温度的水温","ABD","干蒸汽加湿为等温加湿，因此选项A错误。",{"id":6,"name":28,"category":29,"favorite":30},"专业知识（暖通空调专业）","建筑工程",0]