[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-881544":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":12,"analysis":25},881544,569,1,"单选题","关于地源热泵系统，下列说法错误的是( )。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","采用地埋管系统应用面积为2000㎡时，必须作岩土热响应试验",true,{"key":16,"text":17,"correct":18},"B","采用地埋管系统应进行全年空调动态负荷计算",false,{"key":20,"text":21,"correct":18},"C","当地埋管最大释热量和最大吸热量相差不大时，换热器取供冷和供热计算长度的较大值",{"key":23,"text":24,"correct":18},"D","当地埋管最大释热量和最大吸热量相差较大时，换热器取供冷和供热计算长度较小值，并增加辅助冷热源","应为大于5000㎡。",{"id":6,"name":27,"category":28,"favorite":29},"专业知识（暖通空调专业）","建筑工程",0]