[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-881536":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},881536,569,1,"单选题","公共建筑空调冷、热水系统采用二级泵系统的条件，应为各环路压力损失相差悬殊。当采用二级泵系统时，对各个环路压力损失相差数值的具体判据是下列哪一项？( )",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","各环路压力损失相差数值大于90kPa",false,{"key":16,"text":17,"correct":14},"B","各环路压力损失相差数值大于70kPa",{"key":19,"text":20,"correct":21},"C","各环路压力损失相差数值大于50kPa",true,{"key":23,"text":24,"correct":14},"D","各环路压力损失相差数值大于30kPa","",{"id":6,"name":27,"category":28,"favorite":29},"专业知识（暖通空调专业）","建筑工程",0]