[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-881499":3},{"question":4,"library":27},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":25,"analysis":26},881499,569,2,"多选题","对于广州某商场，希望设计三星级绿色建筑，下列哪些技术措施可能是错误的？( )",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","为减少太阳辐射，取消采光中庭的设计",true,{"key":16,"text":17,"correct":14},"B","围护结构体系采用150mm的EPS外保温系统",{"key":19,"text":20,"correct":14},"C","照明功率密度按18W\u002F㎡设计",{"key":22,"text":23,"correct":24},"D","设计通风屋顶",false,"ABC","A的措施在于采光达标的问题；B的问题在于加强保温会导致空调能耗的增加，因为不是24h空调；C的问题在于照明功率密度应该差异化设计，并尽量按照目标值设计，18W\u002F㎡对应的是500lux照度设计的现行值，不能简单化处理。",{"id":6,"name":28,"category":29,"favorite":30},"专业知识（暖通空调专业）","建筑工程",0]