[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-881473":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},881473,569,1,"单选题","当建筑物内的生活用水既有室外管网直接供水，又有自行加压供水时，其给水引入管的设计流量应取( )。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","建筑物生活小时用水量",false,{"key":16,"text":17,"correct":14},"B","建筑物生活用水设计秒流量",{"key":19,"text":20,"correct":14},"C","管网直接部分生活用水设计秒流量与自行加压部分生活用水最大小时水量之和",{"key":22,"text":23,"correct":24},"D","管网直接部分生活用水设计秒流量与自行加压部分供水贮水调节池的设计补水量之和",true,"根据《建筑给水排水设计规范》(GB50015-2003)(2009年版)第3.6.3条规定：当建筑物内的生活用水既有管网直接供水，又有自行加压供水时，应按室外管网直接供水与自行加压供水两部分分别计算设计流量，然后将两者的叠加作为引入管的设计流量。",{"id":6,"name":27,"category":28,"favorite":29},"专业知识（暖通空调专业）","建筑工程",0]