[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-881387":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":12,"analysis":25},881387,569,1,"单选题","某单层厂房设计工艺性空调，采用全空气系统。冬季通过蒸汽加热，干蒸汽加湿处理空气。室内设计参数：24℃、60%；运行时，室内相对湿度低于设计要求。下列哪一项不会造成该问题发生？",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","新风阀开度小于设计值",true,{"key":16,"text":17,"correct":18},"B","加湿器阀门设置有误",false,{"key":20,"text":21,"correct":18},"C","厂房外门、外窗不严密",{"key":23,"text":24,"correct":18},"D","新风量超过设计值","室内湿度偏低，造成的原因是新风过多。",{"id":6,"name":27,"category":28,"favorite":29},"专业知识（暖通空调专业）","建筑工程",0]