[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-881384":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},881384,569,1,"单选题","住宅分户热计量是计量与节能技术的综合，对下列各种共用立管分户热水供暖、计量系统技术方案进行比较，哪项效果最差?( )。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","水平双管系统，每组散热器供水支管上设高阻力恒温控制阀，户用热量表法计量",false,{"key":16,"text":17,"correct":14},"B","水平单管系统，在户系统人口处设户温控制器，通断时间面积法计量",{"key":19,"text":20,"correct":14},"C","水平单管跨越式系统，每组散热器供水支管上设低阻力三通恒温控制阀，户用热量表法计量",{"key":22,"text":23,"correct":24},"D","低温热水地板辐射供暖系统，在各户系统入口处设户温控制器，在分集水器的各支路安装手动流量调节阀，通断时间面积法计量",true,"低温地板辐射供暖宜采用户用热量表法或户用热水表法。《供热计量技术规程》JGJ173-2009第6.1.2条条文说明：(1)通断时间面积法应用的前提是住宅每户需为一个独立的水平串联式系统，低温热水地板辐射供暖系统应为水平并联式系统。(2)通断时间面积法适用按户分环、室内阻力不变的供暖系统。(3)通断时间面积法不能分室或分区控温，以免改变户内环路的阻力。选项D在分集水器各支路安装手动流量调节阀，用户自行调节该阀时，势必会改变各个支管的阻力。综合(1)(2)(3)所述，选项D效果最差。",{"id":6,"name":27,"category":28,"favorite":29},"专业知识（暖通空调专业）","建筑工程",0]