[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-881279":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":24,"analysis":25},881279,569,2,"多选题","当消火栓系统和自动喷水灭火系统合用稳压增压设施时，( )。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","稳压增压流量和气压罐调节容积应按2个系统叠加确定",true,{"key":16,"text":17,"correct":14},"B","稳压增压设施压力应按要求较高的系统确定",{"key":19,"text":20,"correct":14},"C","出水总管管径不应小于DN100",{"key":22,"text":23,"correct":14},"D","与2个系统连接前应分别设置止回阀","ABCD","",{"id":6,"name":27,"category":28,"favorite":29},"专业知识（暖通空调专业）","建筑工程",0]