[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-881244":3},{"question":4,"library":27},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":25,"analysis":26},881244,569,2,"多选题","多层建筑的通风空调风管经过下列哪些房间的隔墙时应设防火阀？( )",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","面积为100㎡的多功能厅",true,{"key":16,"text":17,"correct":18},"B","地下一层面积＜200㎡的水泵房",false,{"key":20,"text":21,"correct":14},"C","人民防空工程中设防火门的房间",{"key":23,"text":24,"correct":18},"D","地下一层面积为500㎡的戊类仓库","AC","下列情况之一的通风、空气调节系统的风管上应设置防火阀：1)穿越防火分区处；2)穿越通风、空气调节机房的房间隔墙和楼板处；3)穿越重要的或火灾危险性大的房间隔墙和楼板处，如重要的会议室、贵宾休息室、多功能厅、贵重物品间等，火灾危险性大的房间，如易燃物品实验室及易燃仓库等；4)穿越变形缝处的两侧；5)垂直风管与每层水平风管交接处的水平管段上，但当建筑内每个防火分区的通风、空气调节系统均独立设置时，该防火分区内的水平风管与垂直总管的交接处可不设置防火阀。题中A为重要房间，C为防火分区。",{"id":6,"name":28,"category":29,"favorite":30},"专业知识（暖通空调专业）","建筑工程",0]