[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-881232":3},{"question":4,"library":27},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":25,"analysis":26},881232,569,2,"多选题","一栋25层建筑，防烟楼梯间及合用前室分别设有机械加压送风系统，所选用的风机全压在满足最不利环路管道的压力损失以外，防烟楼梯间的余压为 A，合用前室的余压为Ba符合现行国家标准规定的正确余压数值是下列哪几项？( )",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","A=50Pa，B=30Pa",false,{"key":16,"text":17,"correct":14},"B","A=40Pa，B=25Pa",{"key":19,"text":20,"correct":21},"C","A=45Pa，B=27.5Pa",true,{"key":23,"text":24,"correct":21},"D","A=50Pa，B=25Pa","CD","",{"id":6,"name":28,"category":29,"favorite":30},"专业知识（暖通空调专业）","建筑工程",0]