[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-881227":3},{"question":4,"library":27},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":25,"analysis":26},881227,569,2,"多选题","某写字楼建筑设计为一个集中式中央空调系统，房间采用风机盘管十新风系统方式，下列确定冷水机组制冷量(不计附加因素)的做法，下列哪几项是错误的?( )。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","冷水机组的制冷量一全部风机盘管(中速)的额定制冷量十新风机组的冷量",false,{"key":16,"text":17,"correct":18},"B","冷水机组的制冷量一全部风机盘管(高速)的额定制冷量十新风机组的冷量",true,{"key":20,"text":21,"correct":18},"C","冷水机组的制冷量一逐项逐时计算的最大小时冷负荷×大于1的同时使用系数",{"key":23,"text":24,"correct":14},"D","冷水机组的制冷量一逐项逐时计算的最大小时冷负荷×小于1的同时使用系数","BC","根据《07节能专篇》，选项D正确，选项C错误。",{"id":6,"name":28,"category":29,"favorite":30},"专业知识（暖通空调专业）","建筑工程",0]