[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-881224":3},{"question":4,"library":27},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":25,"analysis":26},881224,569,2,"多选题","某建筑的一次泵空调水系统，设有3台冷水机组和3台与机组连锁的冷水泵。三台同时运行时，冷水泵的运行参数符合设计要求；当1台冷水机组和1台冷水泵运行时，冷水机组处于低负荷状态，却发现建筑内的部分空调房间实际温度高于设计值。产生上述问题的原因分析及应采取的措施，正确的是下列哪几项？",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","温度高的房间的末端设备的设计冷量不够，应加大末端设备容量",true,{"key":16,"text":17,"correct":18},"B","冷水机组的制冷量不足，应加大制冷机组的容量",false,{"key":20,"text":21,"correct":14},"C","房间的末端设备无自控措施(或自控失灵)，应增加(或检修)自控系统",{"key":23,"text":24,"correct":18},"D","该冷水泵的水流量不能满足要求，应加大水泵流量或再投入一台泵运行","AC","",{"id":6,"name":28,"category":29,"favorite":30},"专业知识（暖通空调专业）","建筑工程",0]