[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-881195":3},{"question":4,"library":27},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":25,"analysis":26},881195,569,2,"多选题","在地面辐射采暖系统中，使用发泡水泥[导热系数为0.09W\u002F(m.K)]代替聚苯乙烯泡沫板[导热系数≤0.04IW\u002F(m3K)]作为楼层间楼板的绝热层时，其合理的厚度约为下列哪几项？",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","90～80mm",false,{"key":16,"text":17,"correct":18},"B","66mm",true,{"key":20,"text":21,"correct":18},"C","44mm",{"key":23,"text":24,"correct":14},"D","30～20mm","BC","《地面辐射供暖技术规程》JGJ1414第3.2.5条、第4.2.3条条文说明：聚苯乙烯泡沫板绝热层厚度为20mm或30mm，则发泡水泥绝热层厚度=20(30)×0.09\u002F0.041=44(66)mm。",{"id":6,"name":28,"category":29,"favorite":30},"专业知识（暖通空调专业）","建筑工程",0]