[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-881184":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},881184,569,1,"单选题","某食品车间长40m、宽10m、层高6m，车间内生产(含电热)设备总功率为215kW，有150名操作工，身着薄棉质工作服坐在流水线旁操作，设计采用全面造风形式消除室内余热并对进风进行两级净化处理(初效和中效过滤)。具体为：采用无冷源的全空气低速送风系统(5台60000m3\u002Fh机组送风，沿车间长度方向布置的送风管设在4m标高处，屋顶设有10台23795m3\u002Fh的排风机进行排风)，气流组织为单侧送(送风速度为2.5m\u002Fs)，顶部排风。车间曾发生多例工人中暑(该地区夏季通风温度为31.2℃)，造成中暑的首选原因应是下列哪一项？",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","新风量不够",false,{"key":16,"text":17,"correct":14},"B","排风量不够",{"key":19,"text":20,"correct":14},"C","送风量与排风量不匹配",{"key":22,"text":23,"correct":24},"D","气流组织不正确",true,"此题无需计算全面通风量，由题意可看出，车间层高6m，单侧送风管设在4m标高，且采用的是无冷源的送风方式。室外新风送不到人员工作区，大部分送风被设置在屋顶的排风机直接排走，故工人中署原因应为气流组织问题。",{"id":6,"name":27,"category":28,"favorite":29},"专业知识（暖通空调专业）","建筑工程",0]