[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-881179":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},881179,569,1,"单选题","下列关于空调冷、热水管道绝热层厚度的计算方法，哪一项是错误的?( )。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","空调水系统采用四管制时，供热管道采用经济厚度方法计算",false,{"key":16,"text":17,"correct":18},"B","空调水系统采用四管制时，供冷管道采用防结露方法计算",true,{"key":20,"text":21,"correct":14},"C","空调水系统采用两管制时，水系统管道分别按冷管道与热管道计算方法计算绝热层厚度，并取二者的较大值",{"key":23,"text":24,"correct":14},"D","空调凝结水管道采用防止结露方法计算","《07节能专篇》第11.3.7条：空调冷、热水管绝热层厚度的计算应按下列原则进行：(1)单冷管道应按防结露方法计算保冷层厚度，再按经济厚度法核算，对比后取其较大值；(2)单热管道应采用经济厚度法计算保温层厚度；(3)冷热合用管道，应分别按冷管道与热管道的计算方法计算绝热厚度，对比后取其较大值。故选项B错，应采用经济厚度法计算保温层厚度。",{"id":6,"name":27,"category":28,"favorite":29},"专业知识（暖通空调专业）","建筑工程",0]