[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-881055":3},{"question":4,"library":27},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":25,"analysis":26},881055,569,2,"多选题","某9层住宅楼设计分户热计量热水采暖系统，哪些做法是错误的?( )。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","供暖系统的总热负荷计入向邻户传热引起的耗热量",true,{"key":16,"text":17,"correct":14},"B","计算系统供、回水干管时计入向邻户传热引起的耗热量",{"key":19,"text":20,"correct":21},"C","户内散热器片数计算时计入向邻户传热引起的耗热量",false,{"key":23,"text":24,"correct":21},"D","户内系统为双管系统，户内入口设置流量调节阀","AB","选项A错误，不应该计入；选项B错误，不计入；选项C正确，户内时应计入；选项D正确，可以调节各户流量。",{"id":6,"name":28,"category":29,"favorite":30},"专业知识（暖通空调专业）","建筑工程",0]