[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-881036":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":24,"analysis":25},881036,569,2,"多选题","进行通风气流组织设计时，应遵循的原则是( )。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","将新鲜空气送到作业地带或操作人员经常停留的工作地点，应避免将有害物吹向工作区",true,{"key":16,"text":17,"correct":14},"B","有害物源散发的有害物气体温度比周围空气高，或者车间存在上升气流，无论有害气体密度大小，均应采用下送上排的方式",{"key":19,"text":20,"correct":14},"C","同时散发热、蒸汽和有害气体，或仅散发密度比空气小的有害气体的生产建筑，除设局部排风外，宜在上部区域进行自然或机械的全面排风，其排风量不宜小于每小时一次换气当房间高度大于6m时，排风量可按每平方米地面面积每小时6立方米计算",{"key":22,"text":23,"correct":14},"D","通风房间气流组织主要方式有：上送上排、下送下排和中间送上下排","ABCD","",{"id":6,"name":27,"category":28,"favorite":29},"专业知识（暖通空调专业）","建筑工程",0]