[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-880981":3},{"question":4,"library":27},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":25,"analysis":26},880981,569,2,"多选题","居住建筑采暖设计计算建筑物内部得热时，下列哪几项是正确的？",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","从建筑热负荷中扣除",false,{"key":16,"text":17,"correct":18},"B","不从建筑热负荷中扣除",true,{"key":20,"text":21,"correct":18},"C","对严寒、寒冷地区的住宅，应从建筑耗热量中扣除",{"key":23,"text":24,"correct":14},"D","均不从建筑耗热量中扣除","BC","《暖规》第4.2.1条条文说明：住宅内部得热(包括炊事、照明、家电和人体散热)是间歇性的，这部分自由热可作为安全量，在确定热负荷时可不予考虑。《住宅建筑规范》GB50368-2005第10.3.1条：严寒、寒冷地区的住宅应以建筑物耗热量指标为控制目标，计算包含围护结构的传热耗热量、空气渗透耗热量和建筑物内部得热量三个部分。计算方法可参考《民用建筑节能设计标准》JGJ26-95第3.0.1条。",{"id":6,"name":28,"category":29,"favorite":30},"专业知识（暖通空调专业）","建筑工程",0]