[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-880949":3},{"question":4,"library":27},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":25,"analysis":26},880949,569,2,"多选题","对于变风量系统设计，下列叙述正确的是( )。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","采用节流型的末端装置时，应在风管内设置静压控制器，根据风管的静压变化来控制风机的总风量",true,{"key":16,"text":17,"correct":14},"B","由于风口变风量会影响室内的气流分布，宜采用扩散性能好的送风口",{"key":19,"text":20,"correct":21},"C","系统的冷热负荷是各区的最大负荷之和",false,{"key":23,"text":24,"correct":14},"D","系统的最小风量必须满足气流分布的最低要求，同时必须大于卫生要求的新风量","ABD","",{"id":6,"name":28,"category":29,"favorite":30},"专业知识（暖通空调专业）","建筑工程",0]