[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-880938":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":12,"analysis":25},880938,569,1,"单选题","某小区供暖系统为6栋建筑供暖，所有用户均设置带自力式恒温阀的散热器供暖系统，与供热管网直接连接，其中一栋楼热力入口设置电动阀，电动阀开启时段为工作日6：30-18：300应采用下列哪种做法？( )",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","各用户热力入口设置定压差阀",true,{"key":16,"text":17,"correct":18},"B","各用户热力入口设置定流量阀",false,{"key":20,"text":21,"correct":18},"C","各用户热力入口设置静态平衡阀",{"key":23,"text":24,"correct":18},"D","各用户热力入口设置动态电动调节阀","各用户为变流量系统；由于其中一栋楼定期启停，除该楼外的各用户供回水压差在该楼热力入口电动阀关闭时均有不同程度的升高。为避免因资用压头升高导致散热器恒温阀长时间小开度工作，宜在用户热力入口设置定压差阀。",{"id":6,"name":27,"category":28,"favorite":29},"专业知识（暖通空调专业）","建筑工程",0]