[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-880908":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},880908,569,1,"单选题","处于建筑物内的燃气管道，下列何处属于严禁敷设的地方?( )。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","居住建筑的楼梯间",false,{"key":16,"text":17,"correct":18},"B","电梯井",true,{"key":20,"text":21,"correct":14},"C","建筑给水管道竖井",{"key":23,"text":24,"correct":14},"D","建筑送风竖井","《高规》第5.3.1条及《建规》第7.2.9条；电梯井应独立设置，井内严禁敷设可燃气体；《城镇燃气设计规范》GB50028-2006第10.2.14条：燃气引入管不得敷设在不使用燃气的进风道、垃圾道等地方(强条)；当有困难时，可从楼梯间引入(高层建筑除外)，但应采用金属管道且引入管阀门宜设在室外。《城镇燃气设计规范》GB50028-2006第10.2.27条：燃气立管可与空气、惰性气体、上下水、热力管道等设在一个公用竖井内，但不得与电线、电气设备或氧气管、进风管、回风管、排气管、排烟管、垃圾道等共用一个竖井。",{"id":6,"name":27,"category":28,"favorite":29},"专业知识（暖通空调专业）","建筑工程",0]