[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-880806":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":25,"analysis":24},880806,569,2,"多选题","某办公建筑选用若干空调制冷设备，下列哪几项表述不符合现行国家标准规定？( )",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","1台螺杆式空气源热泵冷(热)水机组，名义工况的制冷量为400kW，输入功率为146kW",true,{"key":16,"text":17,"correct":14},"B","1台离心式冷水机组，名义工况的制冷量为1250kW，输入功率为250kW",{"key":19,"text":20,"correct":21},"C","1台风冷式接风管的屋顶式空调机组，能效比(EER)为4级",false,{"key":23,"text":24,"correct":14},"D","","ABD",{"id":6,"name":27,"category":28,"favorite":29},"专业知识（暖通空调专业）","建筑工程",0]