[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-880776":3},{"question":4,"library":27},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":25,"analysis":26},880776,569,2,"多选题","某办公楼采用风机盘管+新风的空调设计方案，冬夏兼用，在房间冬季空调热负荷中可以不考虑( )。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","外围护结构的传热负荷",false,{"key":16,"text":17,"correct":18},"B","门窗冷风渗透热负荷",true,{"key":20,"text":21,"correct":18},"C","室内人员的显热负荷",{"key":23,"text":24,"correct":18},"D","室内人员的潜热负荷","BCD","由于设置新风系统，室内通常为正压，因此门窗冷风渗透热负荷可以不考虑。在空调热负荷计算时，室内人员散发的显热量和潜热量都是有利的，通常作为余量，而不考虑扣减。",{"id":6,"name":28,"category":29,"favorite":30},"专业知识（暖通空调专业）","建筑工程",0]