[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-880764":3},{"question":4,"library":27},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":25,"analysis":26},880764,569,2,"多选题","进行某燃气锅炉房的通风设计，下列哪几项符合要求？",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","通风换气次数3次／h，事故通风换气次数6次\u002Fh",false,{"key":16,"text":17,"correct":14},"B","通风换气次数6次\u002Fh，事故通风换气次数10次\u002Fh",{"key":19,"text":20,"correct":21},"C","通风换气次数6次\u002Fh，事故通风换气次数12次\u002Fh",true,{"key":23,"text":24,"correct":21},"D","通风换气次数8次\u002Fh，事故通风换气次数15次\u002Fh","CD","根据《锅炉房设计规范》GB500418第15.3.7条，选项A错误，燃气锅炉房通气至少6次\u002Fh；选项B错误，事故通风至少12次\u002Fh；选项CD正确。",{"id":6,"name":28,"category":29,"favorite":30},"专业知识（暖通空调专业）","建筑工程",0]