[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-880675":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},880675,569,1,"单选题","某大型超市采用接风管的屋顶式风冷空调(热泵)机组，机组的名义制冷量为200kW。对该机组的要求，不符合国家有关标准的应是下列哪一项？( )",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","机组能效比(EER)的等级应不低于4级",false,{"key":16,"text":17,"correct":18},"B","机组的最小机外静压值应不低于500Pa",true,{"key":20,"text":21,"correct":14},"C","机组的噪声值由制造厂确定，并在产品样本中提供",{"key":23,"text":24,"correct":14},"D","机组在名义工况下，其制冷量、制热量不小于名义规定值的95%","屋顶机组名义工况160～240kW时最小机外静压为550Pa。螺杆式风冷热泵机组额定制冷量大于50kW时，要求性能系数不小于2.8。屋顶热泵机组制冷制热性能系数不应低于规定值的95%。",{"id":6,"name":27,"category":28,"favorite":29},"专业知识（暖通空调专业）","建筑工程",0]