[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-880621":3},{"question":4,"library":27},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":25,"analysis":26},880621,569,2,"多选题","不透明围护结构内的空气间层由“密闭”改为“通风”时，会使( )。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","冬季供暖负荷减少",false,{"key":16,"text":17,"correct":18},"B","夏季供冷负荷减少",true,{"key":20,"text":21,"correct":18},"C","冬季供暖负荷增加",{"key":23,"text":24,"correct":14},"D","夏季供冷负荷增加","BC","不透明围护结构(如外墙、屋顶等)内的空气间层由“密闭”改为“通风”时，由于不计算空气间层的热阻，使总传热系数增大，使冬季供暖负荷增加。但通风空气间层改变了太阳辐射热对围护结构热作用，使“冷负荷计算温度”降低。因此，是改善围护结构隔热性能的一种常用措施。此热工计算过程比较复杂，只要求暖通专业设计人员了解其基本原理。",{"id":6,"name":28,"category":29,"favorite":30},"专业知识（暖通空调专业）","建筑工程",0]