[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-880609":3},{"question":4,"library":27},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":25,"analysis":26},880609,569,2,"多选题","下列关于置换通风的说法，正确的是哪几项?( )。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","置换通风不适用在冬季有大量热负荷需要的建筑物外区",true,{"key":16,"text":17,"correct":18},"B","置换通风计算，只针对主要影响室内热舒适的温度进行计算",false,{"key":20,"text":21,"correct":18},"C","夏季置换通风送风温度不宜低于16℃",{"key":23,"text":24,"correct":14},"D","设计中，要避免置换通风与其他气流组织应用于同一空调区","AD","选项A正确，置换通风主要适用于去除冷负荷，《民规》第7.4.7条指出污染源为热源，且对单位面积冷负荷提出了要求；选项B错误，置换通风计算设计原则除了人员活动区垂直温差要求，还有人体周围风速要求及影响空气质量的污染物浓度要求，详《07节能专篇》第4.2.2条；选项C错误，见《民规》第7.4.7-2条，应为“夏季置换通风送风温度不宜低于18℃”；选项D正确，见《民规》第7.4.7-6条条文解释，其他气流组织形式会影响置换气流的流型，无法实现置换通风。",{"id":6,"name":28,"category":29,"favorite":30},"专业知识（暖通空调专业）","建筑工程",0]