[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-880608":3},{"question":4,"library":27},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":25,"analysis":26},880608,569,2,"多选题","下列关于不同类型空调系统的表述，哪几项是正确的？",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","承担多房间的定风量全空气系统(无末端再热)，各个房间热湿负荷不同步变化时，难于同时保障各个房间要求的温度和湿度",true,{"key":16,"text":17,"correct":14},"B","无末端再热的变风量箱可通过调节风量保障承担区域的温度，但难于同时保证承担区域的湿度",{"key":19,"text":20,"correct":21},"C","既有内区又有外区房间的同一楼层采用风机盘管十新风空调系统时，内区房间与外区房间的新风机组分设，共用供水立管，该方案可保证冬季内区房间不过热",false,{"key":23,"text":24,"correct":14},"D","采用多联机的建筑，其直接膨胀式新风机组不宜与室内机共用室外机","ABD","选项C错误，不能共用立管。选项D：新风机组焓差大，室内机焓差小，其冷凝、蒸发压力不一致，不能共用。",{"id":6,"name":28,"category":29,"favorite":30},"专业知识（暖通空调专业）","建筑工程",0]