[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-880565":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},880565,569,1,"单选题","计算低温热水地面辐射采暖的热负荷时，下列哪一项是错误的？",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","比对流采暖系统的室内计算温度低2℃",false,{"key":16,"text":17,"correct":14},"B","对寒冷地区，取对流采暖系统计算总负荷的0.9",{"key":19,"text":20,"correct":14},"C","可以不考虑高度附加",{"key":22,"text":23,"correct":24},"D","局部地区辐射采暖的面积为房间总面积的70%，则需要计入附加系数",true,"根据《暖规》第4.4.4条，在地板辐射采暖用于房间的局部采暖的前提下，且辐射采暖面积≤房间面积的75%时，则需要附加相关系数。选项D中的“局部地区辐射供暖”与“局部地面辐射采暖”含义不完全相符，可判断为错误，因为局部地区辐射供暖可以涵盖其他辐射供暖形式。另外，本题还可以采用排除法在确定ABC三个选项完整正确的前提下还可以利用排除法来判断D选项是错误的。ABC三个选项在《暖规》第4.4.4条、《地面辐射供暖技术规程》JGJ1414第3.3.2条、第3.3.6条有表述。",{"id":6,"name":27,"category":28,"favorite":29},"专业知识（暖通空调专业）","建筑工程",0]