[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-880519":3},{"question":4,"library":27},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":25,"analysis":26},880519,569,2,"多选题","有关地板送风系统，下列说法正确的是哪些项?( )。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","地板送风的送风温度较置换通风低，系统所负担的冷负荷也大于置换通风",true,{"key":16,"text":17,"correct":18},"B","分层空调无论用于冬季还是夏季均有好的节能效果",false,{"key":20,"text":21,"correct":14},"C","地板送风应避免与其他气流组织形式应用于统一空调区",{"key":23,"text":24,"correct":14},"D","地板送风设计时应将热分层高度维持在室内人员活动区","ACD","选项A正确，见《民规》第7.4.8-1条条文解释；选项B错误，见《公建节能》第5.3.22条文解释，“与全室性空调方式相比，分层空调夏季可节省冷量30%左右，但在冬季供暖工况下运行时并不节能”；选项C正确，见《民规》第7.4.8-4条条文解释，其他气流组织会破坏房间内的空气分层；选项D正确，《09技术措施》第5.16.3-4条，“工作区的热力分层高度根据热源的坐、站姿确定，宜为1.2～1.8m”",{"id":6,"name":28,"category":29,"favorite":30},"专业知识（暖通空调专业）","建筑工程",0]