[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-880512":3},{"question":4,"library":27},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":25,"analysis":26},880512,569,2,"多选题","《公建节能》对集中供暖系统确定耗电输热比(EHR)的允许值与下列因素的关系，哪些是错误的？( )",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","与室外供暖主管线的长度成正比",false,{"key":16,"text":17,"correct":14},"B","与设计供回水温差成反比",{"key":19,"text":20,"correct":21},"C","与管网的实际比摩阻成正比",true,{"key":23,"text":24,"correct":21},"D","与循环水泵的传动效率成反比","CD","耗电输热比(EHR)的允许值，是按照不同主管线长度对比摩阻的规定确定的，与实际比摩阻无关。水泵的传动效率是用以计算EHR的实际值的，与确定EHR的允许值无关。",{"id":6,"name":28,"category":29,"favorite":30},"专业知识（暖通空调专业）","建筑工程",0]