[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-880487":3},{"question":4,"library":27},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":25,"analysis":26},880487,569,2,"多选题","关于人防工程的通风设计，过滤吸收器的额定风量的确定，哪几项是错误的？",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","不小于最大的计算新风量",true,{"key":16,"text":17,"correct":14},"B","不小于战时清洁通风的计算新风量",{"key":19,"text":20,"correct":21},"C","不小于战时滤毒通风的计算新风量",false,{"key":23,"text":24,"correct":14},"D","不小于战时要求的隔绝通风量","ABD","《人民防空地下室设计规范》GB50038-2005第5.2.16条：“严禁小于”；第5.3.3-3条：“滤毒新风量”，选项C正确。",{"id":6,"name":28,"category":29,"favorite":30},"专业知识（暖通空调专业）","建筑工程",0]