[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-880476":3},{"question":4,"library":27},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":25,"analysis":26},880476,569,2,"多选题","某建筑面积为5000㎡的办公楼采用变制冷剂流量多联分体式空气调节系统，其新风供应方案选择正确的是哪几项？",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","开窗获取新风",false,{"key":16,"text":17,"correct":14},"B","风机直接进入新风到室内机的回风处",{"key":19,"text":20,"correct":21},"C","设置新风机组",true,{"key":23,"text":24,"correct":21},"D","采用全热交换装置","CD","建筑面积为5000㎡的办公楼，面积较大，选项A中开窗获取新风不可能满足要求；选项B中风机直接进入新风到室内机的回风处增大了室内机的负荷，室内的参数也可能达不到要求，另外还不节能，故选项B非优方案；选项C、D满足要求。",{"id":6,"name":28,"category":29,"favorite":30},"专业知识（暖通空调专业）","建筑工程",0]