[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-880470":3},{"question":4,"library":27},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":25,"analysis":26},880470,569,2,"多选题","下列关于高层建筑加压送风系统的设计要求，正确的是( )。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","防烟楼梯间正压为40～50Pa，加压风口宜每隔2～3层设置1个",true,{"key":16,"text":17,"correct":18},"B","一个剪刀楼梯间应分别设置2个加压送风系统",false,{"key":20,"text":21,"correct":14},"C","层数超过32层的防烟楼梯间，其送风系统和送风量应分段设计",{"key":23,"text":24,"correct":18},"D","设加压送风的防烟楼梯间，无外窗的前室应设加压送风系统","AC","",{"id":6,"name":28,"category":29,"favorite":30},"专业知识（暖通空调专业）","建筑工程",0]