[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-880453":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},880453,569,1,"单选题","关于防空地下室防护通风的设计，下列哪一项正确？",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","穿墙通风管，应采取可靠的防护密闭措施",false,{"key":16,"text":17,"correct":14},"B","战时为物资库的防空地下室，应在值班室设置测压装置",{"key":19,"text":20,"correct":14},"C","防爆波活门的额定风量不应小于战时隔绝式通风量",{"key":22,"text":23,"correct":24},"D","过滤吸收器的额定风量必须大于滤毒通风时的进风量",true,"依据《人民防空地下室设计规范》GB50038-2005第5.2.13条，选项A错误，应为“穿越防护密闭墙的通风管”；根据第5.2.1条、第5.2.17条，选项B错误；第5.2.10条，选项C错误，应为“战时清洁通风量”；根据第5.2.16条，选项D正确，“严禁小于”等同“必须大于”。",{"id":6,"name":27,"category":28,"favorite":29},"专业知识（暖通空调专业）","建筑工程",0]