[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-880437":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},880437,569,1,"单选题","下列哪一项小区锅炉房的设计方案是错误的？( )",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","热水系统的循环水泵进口干管上装设高于系统静压的泄压放气管",false,{"key":16,"text":17,"correct":14},"B","补水泵的扬程不应小于补水点压力加35～50kPa富余量",{"key":19,"text":20,"correct":21},"C","高位膨胀水箱与热水系统连接的位置宜设在循环水泵进口干管处；高位膨胀水箱的最低水位应高于热水系统最高点1m以上",true,{"key":23,"text":24,"correct":14},"D","补水泵不宜少于2台，其中1台备用","",{"id":6,"name":27,"category":28,"favorite":29},"专业知识（暖通空调专业）","建筑工程",0]