[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-880242":3},{"question":4,"library":27},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":25,"analysis":26},880242,569,2,"多选题","下列关于空调冷负荷的算法中，不正确的是( )。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","空调冷负荷应采用逐时计算法计算，并乘以一定的附加系数",true,{"key":16,"text":17,"correct":18},"B","三速开关控制的风机盘管空调系统的冷负荷按各项冷负荷的最大值累计计算",false,{"key":20,"text":21,"correct":14},"C","变风量空调系统的冷负荷按各项冷负荷的最大值累计计算",{"key":23,"text":24,"correct":14},"D","对于间歇空调的情况，直接采用典型设计日逐时空调冷负荷计算结果","ACD","对于间歇空调的情况，在典型设计日逐时计算结果的基础上，还要考虑间歇附加。",{"id":6,"name":28,"category":29,"favorite":30},"专业知识（暖通空调专业）","建筑工程",0]