[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-880168":3},{"question":4,"library":27},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":25,"analysis":26},880168,569,2,"多选题","在用天然气为燃料的锅炉房事故排风系统设计时，下列哪几项是正确的？",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","排风机应采用防爆风机",true,{"key":16,"text":17,"correct":18},"B","排出室外的排风口应低于室外进风口2m",false,{"key":20,"text":21,"correct":18},"C","排出室外的排风口应低于室外进风口6m",{"key":23,"text":24,"correct":14},"D","室内排风口应高于房间地面2m以上","AD","",{"id":6,"name":28,"category":29,"favorite":30},"专业知识（暖通空调专业）","建筑工程",0]