[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-880160":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},880160,569,1,"单选题","机械循环热水供暖系统的恒压点(膨胀水箱膨胀管或补水定压装置的补水管与系统的接点)，当设置于循环水泵的吸入口处，循环水泵运行时，( )。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","系统的各点工作压力均会高于静压，升高值为循环水泵的铭牌扬程",false,{"key":16,"text":17,"correct":14},"B","系统的各点工作压力均会高于静压，升高值为循环水泵工作点的扬程",{"key":19,"text":20,"correct":21},"C","系统的各点工作压力均会高于静压，各点的升高值是不同的",true,{"key":23,"text":24,"correct":14},"D","系统供水管的工作压力均会高于静压，回水管的工作压力均会低于静压，波动值为循环水泵工作点的扬程","循环水泵运行时，各点工作压力的升高值应为循环水泵工作点的扬程，减去自循环水泵出口至该点的阻力损失，因阻力损失不同，各点的升高值是不同的。",{"id":6,"name":27,"category":28,"favorite":29},"专业知识（暖通空调专业）","建筑工程",0]