[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-880150":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},880150,569,1,"单选题","某23层办公大楼的空调水系统为闭式系统，冷水机组、冷水循环泵和膨胀水箱均置于建筑的最高屋面处，系统调试时，冷水循环泵和供回水管路的振动很大。分析产生问题的原因，是下列哪一项？( )",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","冷水循环泵的扬程选择过高",false,{"key":16,"text":17,"correct":14},"B","冷水循环泵的流量过大",{"key":19,"text":20,"correct":14},"C","冷水循环泵与膨胀水箱的距离过大",{"key":22,"text":23,"correct":24},"D","冷水供回水管路中有空气",true,"",{"id":6,"name":27,"category":28,"favorite":29},"专业知识（暖通空调专业）","建筑工程",0]